Standard Breaker Sizes NEC & Fuse Ratings

Free online tool • 2026 NEC Compliant

NEC Table 240.6(A) defines standard overcurrent protection device (breaker and fuse) ratings. When calculations result in non-standard ratings, the code generally allows rounding up to the next standard size. Use the breaker sizing calculator below, and reference the official standard amperage charts on this page.

Recommended Sizing

NEC Standard Size
25 Amp

Breaker Type: Standard Inverse-Time

Minimum Wire Size (Copper)10 AWG
Wire Ampacity (75ยฐC Rating)35A
Conduit Size (Rough Guide)3/4"
Calculated Load (Amps)25.0A

NEC Reference Note: 125% multiplier applied for continuous loads per NEC 210.20(A).

How to Use This Calculator

Calculate circuit load

Sum continuous loads at 125% and non-continuous loads at 100%.

Find required ampacity

Select a conductor with an ampacity rating matching or exceeding the calculated load.

Compare to standard sizes

If the conductor ampacity does not match a standard size under 800A, round up to the next standard breaker rating.

Frequently Asked Questions

What are standard breaker sizes?

Per NEC 240.6(A), standard inverse-time circuit breaker ratings are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, and 6000 Amps. Additional standard fuse ratings include 1, 3, 6, and 10 Amps.

Can I round up to the next standard breaker size?

Yes. Under NEC 240.4(B), you can use the next standard overcurrent device rating (rounding up) if the calculated conductor ampacity does not correspond to a standard size, provided the rating does not exceed 800 amps and the circuit is not a multioutlet branch circuit.