Ductless Mini Split Breaker & Wire Size
Free online tool • 2026 NEC Compliant
Unlike most appliances, ductless mini split breaker size is not calculated from BTU rating alone โ NEC 440.22 requires sizing based on the Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOCP) values printed on the outdoor condenser's nameplate. A small single-zone 9,000โ12,000 BTU unit typically needs a 15A or 20A circuit, while larger single-zone and multi-zone systems often require 20Aโ30A at 208/240V.
Recommended Sizing
NEC Standard SizeBreaker Type: Standard Inverse-Time
NEC Reference Note: 125% multiplier applied for continuous loads per NEC 210.20(A).
How to Use This Calculator
Find the outdoor unit nameplate
Locate the MCA and MOCP values on the condenser's data plate โ never estimate from BTU rating alone.
Select a breaker at or below MOCP
Choose the largest standard breaker size that does not exceed the MOCP rating.
Select wire meeting or exceeding MCA
Wire ampacity must be equal to or greater than the MCA value.
Confirm dedicated circuit and disconnect
Verify a dedicated circuit and a disconnect located within sight of the outdoor unit per NEC 440.14.
Frequently Asked Questions
What size breaker does a mini split need?
It depends on the unit. Small single-zone systems (9kโ12k BTU) commonly use a 15A or 20A breaker at 115โ230V. Larger single-zone and multi-zone systems (18kโ36k+ BTU) often require 20Aโ30A double-pole breakers at 208/240V. Always use the MCA/MOCP values on the outdoor unit's nameplate rather than estimating from BTU.
Do mini splits need a dedicated circuit?
Yes. Mini split condensers require a dedicated branch circuit sized to the manufacturer's nameplate rating, per NEC Article 440. A disconnect within sight of the outdoor unit is also required.
What is MCA and MOCP on a mini split nameplate?
MCA (Minimum Circuit Ampacity) is the minimum wire ampacity required for the circuit. MOCP (Maximum Overcurrent Protection) is the largest breaker size permitted. The installed breaker must be at or below the MOCP value and the wire must meet or exceed the MCA value.
Specific Sizing Guides & Calculators
Electric Range Circuit Breaker & Wire Size
What size breaker does an electric range need? Standard ranges require a 40A or 50A double-pole breaker on a dedicated 240V circuit per NEC.
Electric Water Heater Breaker & Wire Size
What size breaker does a water heater need? Standard 4500W electric water heaters require a 30A double-pole breaker with 10 AWG copper wire per NEC rules.
Electric Dryer Breaker & Wire Size
Standard electric dryers require a 30 amp double-pole breaker with 10 AWG copper wire on a 240V circuit. Learn how to size your dryer circuit.
Standard Breaker Sizes NEC & Fuse Ratings
Standard breaker sizes per NEC 240.6(A). Comprehensive chart of standard circuit breaker amperage ratings from 15A to 6000A for residential & commercial.
3-Phase Circuit Breaker & Wire Size Calculator
Calculate 3-phase circuit breaker and wire size. Supports 208V, 240V, and 480V three-phase systems for motors, heaters, and continuous commercial loads.
Hot Tub & Spa Breaker Size (NEC Article 680)
What size breaker does a hot tub need? Most hardwired 240V spas require a 50 amp GFCI breaker with 6 AWG copper wire per NEC Article 680.
RV Breaker Size: 30 Amp vs 50 Amp Service
What size breaker for an RV outlet? 30A service uses a single-pole 120V breaker with 10 AWG wire; 50A service uses a double-pole breaker with 6 AWG wire.
Built-In Electric Wall Oven Breaker & Wire Size
What size breaker for a built-in wall oven? Most single wall ovens need a 20A-30A double-pole 240V breaker; double wall ovens often require 30A-40A.
Garbage Disposal Breaker & Wire Size
What size breaker for a garbage disposal? Most residential disposals require a dedicated 15A or 20A 120V circuit with 14 or 12 AWG copper wire.
Submersible Well Pump Breaker & Wire Size
What size breaker for a well pump? Sizing depends on motor horsepower and full-load amps per NEC Article 430, typically 15A to 30A for residential pumps.
Dishwasher Breaker & Wire Size
What size breaker for a dishwasher? Most residential dishwashers need a dedicated 15A or 20A 120V circuit with GFCI protection per NEC 210.8(D).
Related Calculators
Conduit Fill Calculator
Calculate NEC-compliant conduit fill percentages.
Voltage Drop Calculator
Determine voltage drop across wire runs.
Breaker Size Calculator
Find the correct breaker size for your circuit.
Wire Gauge Chart
Reference AWG diameters, ampacities, and limits.
Box Fill Calculator
Verify NEC 314.16 junction box fill compliance.
Grounding Calculator
Size EGC and GEC conductors per NEC Article 250.
Conduit Bending Calculator
Calculate offset, saddle, and stub-up bend marks.
EV Charger Calculator
Size Level 2 EV charger circuits per NEC 625.42.