1-1/2" Conduit Wire Fill Calculator
Free online tool • 2026 NEC Compliant
1.5-inch conduit (trade size 1-1/2") is one of the most common sizes used in residential and commercial branch circuit and feeder runs. Select your conduit type and wire gauges below to calculate NEC-compliant fill. Per NEC Chapter 9, Table 1, the maximum fill for three or more conductors is 40% of the conduit's internal cross-sectional area.
Conductors
THHN / THWN-2Results
PASSTotal Conductors
3
Wire Area Used
0.0399 in²
Remaining Space
0.1733 in²
How to Use This Calculator
Select conduit type
Choose EMT, PVC Schedule 40/80, RMC, or FMC.
Set trade size to 1-1/2"
The calculator pre-selects 1-1/2" conduit for this page.
Add your wire rows
Enter each wire gauge and quantity.
Check fill result
Verify the calculated fill percentage is at or below the NEC limit.
Frequently Asked Questions
How many 12 AWG wires fit in 1-1/2" conduit?
In 1-1/2" EMT (internal area 2.036 in², 40% limit = 0.814 in²), each 12 AWG THHN wire occupies 0.0133 in². You can fit approximately 61 conductors. However, actual fills should always be checked against the NEC fill percentage for your specific number of conductors.
How many 10 AWG wires fit in 1-1/2" conduit?
In 1-1/2" EMT, at the 40% fill limit (0.814 in²), each 10 AWG THHN wire occupies 0.0211 in². You can fit approximately 38 conductors.
Specific Sizing Guides & Calculators
1-Inch Conduit Wire Fill Calculator
Calculate how many wires fit in 1 inch conduit. Free 1" EMT and PVC fill calculator per NEC 40% fill rules. Instantly check capacity for any wire gauge.
Cat 6 & Low-Voltage Conduit Fill Calculator
Calculate how many Cat 6 or Cat 6a ethernet cables fit inside EMT or PVC conduit. Compliant with NEC 40% fill rule for low-voltage communications wiring.
Related Calculators
Conduit Fill Calculator
Calculate NEC-compliant conduit fill percentages.
Voltage Drop Calculator
Determine voltage drop across wire runs.
Breaker Size Calculator
Find the correct breaker size for your circuit.
Wire Gauge Chart
Reference AWG diameters, ampacities, and limits.
Box Fill Calculator
Verify NEC 314.16 junction box fill compliance.
Grounding Calculator
Size EGC and GEC conductors per NEC Article 250.
Conduit Bending Calculator
Calculate offset, saddle, and stub-up bend marks.
EV Charger Calculator
Size Level 2 EV charger circuits per NEC 625.42.