NEC Table 250.66 Grounding Electrode Conductor Table Explained
Free online tool • 2026 NEC Compliant
NEC Table 250.66 sets the minimum size for the grounding electrode conductor (GEC) โ the conductor that bonds your electrical service to the grounding electrode system (ground rods, water pipe, or concrete-encased electrode). The required GEC size scales with the size of your service-entrance conductors, not your panel's amperage rating directly. The table also caps GEC size for specific electrode types: rod, pipe, or plate electrodes never require larger than 6 AWG copper (250.66(A)), and concrete-encased electrodes never require larger than 4 AWG copper (250.66(B)), regardless of service size.
Select the rating of the circuit breaker or fuse protecting this branch circuit or feeder.
Minimum Required Size
NEC Table 250.122copper ยท Equipment Grounding Conductor (EGC)
NEC Table 250.122 Reference Table (Copper)
| OCD Rating | Min Copper Size |
|---|---|
| 15 A | 14 AWG |
| 20 A | 12 AWG |
| 30 A | 10 AWG |
| 40 A | 10 AWG |
| 60 A | 10 AWG |
| 100 A | 8 AWG |
| 200 A | 6 AWG |
| 300 A | 4 AWG |
| 400 A | 3 AWG |
| 500 A | 2 AWG |
| 600 A | 1 AWG |
| 800 A | 1/0 AWG |
| 1000 A | 2/0 AWG |
| 1200 A | 3/0 AWG |
| 1600 A | 4/0 AWG |
| 2000 A | 250 kcmil |
NEC Reference: The EGC runs with the branch circuit or feeder. For a 20 A overcurrent device, use minimum 12 AWG copper wire.
How to Use This Calculator
Identify service-entrance conductor size
Find the AWG or kcmil size of your incoming service conductors (copper or aluminum).
Look up the matching GEC size
Use NEC Table 250.66 to find the minimum required GEC size for that conductor size.
Apply electrode-type caps
If connecting only to rod/pipe/plate electrodes, cap at 6 AWG copper; for concrete-encased electrodes, cap at 4 AWG copper.
Select conductor material
Confirm whether you are sizing in copper or aluminum, since the table lists both.
Frequently Asked Questions
How do I read NEC Table 250.66?
Find your service-entrance conductor size (copper or aluminum) in the table's left columns, then read across to find the minimum required grounding electrode conductor (GEC) size. For example, 2 AWG through 1/0 AWG copper service conductors require a 6 AWG copper GEC; 250 kcmil through 500 kcmil copper service conductors require a 2/0 AWG copper GEC.
Why is my GEC smaller than expected for a large service?
Table 250.66 includes size caps for specific electrode types. A GEC connecting only to rod, pipe, or plate electrodes is never required to be larger than 6 AWG copper, even on very large services, per NEC 250.66(A). A GEC to a concrete-encased electrode is capped at 4 AWG copper per 250.66(B).
Does GEC size depend on panel amperage or wire size?
GEC size is based on the size of the service-entrance (or largest ungrounded) conductors, not the panel's amp rating directly. Two services rated the same amperage can require different GEC sizes if they use different conductor sizes to achieve that rating.
Specific Sizing Guides & Calculators
Related Calculators
Conduit Fill Calculator
Calculate NEC-compliant conduit fill percentages.
Voltage Drop Calculator
Determine voltage drop across wire runs.
Breaker Size Calculator
Find the correct breaker size for your circuit.
Wire Gauge Chart
Reference AWG diameters, ampacities, and limits.
Box Fill Calculator
Verify NEC 314.16 junction box fill compliance.
Grounding Calculator
Size EGC and GEC conductors per NEC Article 250.
Conduit Bending Calculator
Calculate offset, saddle, and stub-up bend marks.
EV Charger Calculator
Size Level 2 EV charger circuits per NEC 625.42.